3114 Isolated universal converter


Isolated universal converter-3114
Model: 3114
Make: PR Electronics
Origin: Denmark
  • Input for RTD, TC, Ohm, potentiometer, mA and V
  • Slimline housing of 6 mm
  • 2-wire supply >15 V
  • Output for current and voltage
  • Can be supplied separately or installed on power rail, PR 9400
         

$202.00

Email
Compare

Application

  • Linearized, electronic temperature measurement with RTD or TC sensor.
  • Conversion of linear resistance variation to a standard analog current / voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
  • Power supply and signal isolator for 2-wire transmitters.
  • Process control with standard analog output.
  • Galvanic separation of analog signals and measurement of floating signals.
  • The device can be mounted in Safe area or in Zone 2 and Cl. 1 Div 2. area.

Advanced features

  • When 3114 is used in combination with the 4501 display / programming front and ConfigMate 4590, all operational parameters can be modified to suit any application.

Technical characteristics

  • A green / red front LED indicates normal operation and malfunction.
  • 3-port 2.5 kVAC galvanic isolation.
Category:

Environmental Conditions

Operating temperature -25°C to +70°C
Storage temperature -40°C to +85°C
Calibration temperature 20…28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & measurement / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD) 113 x 6.1 x 115 mm
Weight approx. 70 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13 x 2.5 mm2 / AWG 26…12 stranded wire
Screw terminal torque 0.5 Nm
2…25 Hz ±1.6 mm
25…100 Hz ±4 g

Common specifications

Supply

Supply voltage 16.8…31.2 VDC
Fuse 400 mA SB / 250 VAC
Max. required power 1.2 W
Internal power dissipation 0.4 W (typ.) / 0.65 W (max.)

Isolation voltage

Isolation voltage, test / working 2.5 kVAC / 300 VAC (reinforced)
Zone 2 / Div. 2 250 VAC

Response time

Temperature input (0…90%, 100…10%) ≤ 1 s
mA / V input (0…90%, 100…10%) ≤ 400 ms
Signal / noise ratio > 60 dB
Programming ConfigMate 4590
Accuracy Better than 0.1% of selected range
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span

Input specifications

RTD input

RTD type Pt10/20/50/100/200/250/300/Pt400/500/1000; Ni50/100/120/1000
Cable resistance per wire (max.) 50 Ω
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Yes
Short circuit detection < 15 Ω

Potentiometer input

Potentiometer min….max. 10 Ω…100 kΩ

TC input

Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
CJC via internally mounted sensor ±(2.0°C + 0.4°C * Δt)
Δt = Internal temp.-ambient temp.
Sensor error detection Yes
Sensor error current: When detecting / else Nom. 2 μA / 0 μA

Current input

Measurement range 0…23 mA
Programmable measurement ranges 0…20 and 4…20 mA
Input resistance Nom. 20 Ω + PTC 50 Ω

Voltage input

Measurement range 0…12 VDC
Programmable measurement ranges 0/0.2…1, 0/1…5, 0/2…10 VDC
Input resistance Nom. 10 MΩ
2-wire transmitter supply > 15 V / 20 mA

Output specifications

Current output

Signal range 0…23 mA
Programmable signal ranges 0…20/4…20/20…0/20…4 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Sensor error indication 0 / 3.5 / 23 mA / none
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA
Current limit ≤ 28 mA

Voltage output

Signal range 0…10 VDC
Programmable signal ranges 0/0.2…1; 0/1…5 ; 0/2…10; 1…0.2/0; 5…1/0; 10…2/0 V
Load (@ voltage output) ≥ 10 kΩ
*of span = of the currently selected measurement range

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011

Approvals

ATEX 2014/34/EU KEMA 10ATEX0147 X
IECEx KEM 10.0068X
FM FM17US0004X / FM17CA0003X
DNV-GL Marine Stand. f. Certific. No. 2.4 V1-7-2
UL UL 61010-1
EAC Ex TR-CU 012/2011 RU C-DK.GB08.V.00410
CCOE P337347/1

Data sheet