3112 Pt100 converter – isolated


Pt100 converter – isolated-3112

Model: 3112
Make: PR Electronics
Origin: Denmark

  • Excellent accuracy, better than 0.05% of span
  • Slimline housing of 6 mm
  • Excellent EMC performance and 50/60 Hz noise suppression
  • Selectable < 30 ms / 300 ms response time
  • Pre-calibrated temperature ranges selectable via DIP-switches
        

$143.00

Email
Compare

Application

  • The 3112 temperature converter measures a standard 2-, 3- or 4-wire Pt100 temperature sensor, and provides an isolated analog voltage or current output.
  • High 3 port isolation provides surge suppression and protects the control system from transients and noise.
  • The 3112 can be mounted in the safe area or in Zone 2 / Division 2 areas.
  • Approved for marine applications.

Technical characteristics

  • Flexibly powered by 24 VDC (±30%) via power rail or connectors.
  • < 30 ms fast response time with simultaneous sensor error detection when selected.
  • Selectable 300 ms response time when signal dampening is needed.
  • Excellent conversion accuracy in all available ranges, better than 0.05% of span.
  • Meeting the NAMUR NE21 recommendations, the 3112 provides top measurement performance in harsh EMC environments.
  • The device meets the NAMUR NE43 standard defining out of range and sensor error output values.
  • A visible green LED indicates operational status of the unit and the input sensor.
  • All terminals are protected against overvoltage and polarity error.
  • High galvanic isolation of 2.5 kVAC.
  • Excellent signal/noise ratio of > 60 dB.

Mounting / installation / programming

  • Selectable DIP-settings for easy configuration of more than 1000 factory calibrated measurement ranges.
  • The narrow 6 mm housing allows up to 165 units to be mounted per meter of DIN rail, without any air gap between units.
  • Wide ambient temperature range of -25…+70°C.
Category:
Weight 0.070 kg
Dimensions 115 × 6.1 × 113 mm

Environmental Conditions

Operating temperature -25°C to +70°C
Storage temperature -40°C to +85°C
Calibration temperature 20…28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & measurement / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD) 113 x 6.1 x 115 mm
Weight approx. 70 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13 x 2.5 mm2 / AWG 26…12 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2…25 Hz ±1.6 mm
25…100 Hz ±4 g

Common specifications

Supply

Supply voltage 16.8…31.2 VDC
Max. required power 0.7 W

Isolation voltage

Isolation voltage, test / working 2.5 kVAC / 300 VAC (reinforced)
Zone 2 / Div. 2 250 VAC

Response time

Response time (0…90%, 100…10%) < 30 ms / 300 ms (selectable)
Accuracy Better than 0.05% of selected range
Signal / noise ratio > 60 dB
Programming DIP-switches
Signal dynamics, input 23 bit
Signal dynamics, output 18 bit
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span
Incorrect DIP-switch setting identification 0 V / 0 mA output; LED 0.5 s / 1 Hz

Input specifications

RTD input

Temperature range, Pt100 -200…+850°C
Min. measurement range (span) 10°C
Accuracy: the greater of Better than 0.05% of span or 0.1°C
Temperature coefficient: the greater of 0.02°C/°C or ≤ ±0.01%/°C
Sensor current < 150 µA
Sensor cable resistance < 50 Ω per wire
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Yes – selectable via DIP-switch
Broken sensor detection > 800 Ω
Shorted sensor detection < 18 Ω

Output specifications

Common output specifications

Updating time 10 ms

Current output

Signal range 0…23 mA
Programmable signal ranges 0 / 4…20 mA
Sensor error indication (0…20 mA) 0 mA or 23 mA / OFF
Sensor error indication (4…20 mA) 3.5 mA or 23 mA / acc. to NAMUR NE43 or OFF
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Current limitation @ low output load < 60 mA peak / < 4 mA average

Voltage output

Programmable signal ranges 0/1…5 and 0/2…10 V
Sensor error indication 0 V / 10% above the max. / none
Open output < 18 V

Observed authority requirements

EMC 2014/30/EU
LVD 2014/35/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011

Approvals

ATEX 2014/34/EU KEMA 10ATEX0147 X
IECEx KEM 10.0068X
FM FM17US0004X / FM17CA0003X
DNV-GL Marine Stand. f. Certific. No. 2.4 V1-7-2
UL UL 61010-1

Data sheet


Manuals