Dark Light
, , , ,

NT 100-DN-CO Hilscher

Hilscher
Availability:

Available on backorder


Make: Hilscher | Origin: Germany | Condition: New

Gateway DeviceNet to CANopen | High-end gateway for demanding conversions

✔ Connects DeviceNet and CANopen networks bidirectionally.
✔ Supports up to 63 DeviceNet Slaves or 126 CANopen Nodes.
✔ I/O data conversion in under 10 ms.
✔ Quick device exchange via memory card.
✔ Loadable firmware for flexible conversions.
✔ USB interface for diagnostics and configuration. 

826.00

Available on backorder

NT 100-DN-CO DeviceNet to CANopen supports the following protocols:

  • CANopen Slave
  • DeviceNet Slave
  • DeviceNet Master
  • CANopen Master

netTAP 100 connects to communication networks and acts as a Gateway for sophisticated conversions between one Real-Time Ethernet protocol (2-port) and one fieldbus protocol or one serial automation protocol as well as between two fieldbus protocols as well as between one fieldbus protocol and one serial automation protocol. Licensed Master functionality is unrestricted.

A memory card slot allows the user to save firmware and configuration data on a removable card. In case of problems, the user can continue operation within a few seconds by removing the memory card from the netTAP 100 and connecting it to a spare unit.

Apart from s dard protocols, netTAP 100 supports the programming of special serial protocols with the Lua-based scripting language netSCRIPT. A full-featured development environment (included within the delivery) allows the comfortable and rapid programming of any proprietary serial protocol as well as the I/O data preprocessing and further processing during the conversion into the secondary I/O field protocol.

IEPSOLnical Data – NT 100-DN-CO DeviceNet to CANopen:

ProductProduct nameNT 100-DN-CO
Part number1717.160
Brief descriptionGateway DeviceNet to CANopen
Communication controllernetXnetX 100
Integrated MemoryRAM8 MB SDRAM
FLASH4 MB serial Flash
Memory cardType and sizeSD or MMC card, max. 2 GByte
Power supplySupply voltage24 V DC ± 6 V
Maximum Current at 24 V (typically)130 mA
Typical power consumption3,2 W
ConnectorMini-COMBICON, 2-pin
Reverse voltage protectionyes
Requirement to the power supplyFor UL compliant usage: Device shall be supplied by an isolated voltage source
Communication interface X2Communication s dardDeviceNet
Interface typeISO 11898, optically isolated
ConnectorCOMBICON, 5-pin
Communication interface X3Communication s dardCANopen
Interface typeISO 11898, optically isolated
ConnectorD-Sub, plug, 9-pin
Diagnostic interfaceTypeUSB
ConnectorMini-USB, 5-pin
DisplaysLED displaysSYS System status
APL Application status
MNS Module/ Network Status Duo LED red/green
CAN Communication status Duo LED red/green
Operating elementsNetwork addressNetwork address, 2 rotary switches
Permitted ambient conditionsAmbient temperature (operation)0 … + 60 °C
Humidityno condensation permitted
Altitude0 … 2000 m
Pollution degreeFor UL-compliant usage: Device must be used in a pollution degree 2 environment
DeviceDimensions (L x W x H)100 x 52 x 70 mm (without connector)
Weightappr. 150 g
Degree of protectionIP 20
Mountingon DIN rail EN 60715
ConfigurationConfiguration softwareSYCON.net
ConformityRoHSYes
UL certificationULThe device is UL 508 certified
UL fileUL-File No E334100
Conformance with EMC directivesCE signYes
UKCA signYes
EmissionCISPR 11 Class A
ImmunityEN 61131-2 / BS EN 61131-2
Electrostatic discharge (ESD) according to EN 61000-4-2 / BS EN 61000-4-2 (Air discharge method)±8 kV Criterion B
Electrostatic discharge (ESD) according to EN 61000-4-2 / BS EN 61000-4-2 (Contact discharge method)±4 kV Criterion A
Fast transient interferences (Burst), according to EN 61000-4-4 / BS EN 61000-4-4±2 kV Criterion B
Surge voltage, according to EN 61000-4-5 / BS EN 61000-4-5 (Communication and data lines)±1 kV Criterion B

 