Dark Light
, , , ,

NT 100-RE-EN Hilscher

Hilscher
Availability:

Available on backorder


Make: Hilscher | Origin: Germany | Condition: New

Gateway Real-Time Ethernet to Ethernet | High-end gateway for demanding conversions

✔ Integrates a subordinate Real-Time Ethernet network into another Ethernet system, and vice versa
✔ Master for up to 200 EtherCAT Slaves, 128 PROFINET IO-Devices, 64 EtherNet/IP Adapter, 511 Sercos Slaves
✔ Shortest I/O data conversion period of less than 10 ms
✔ Device exchange in seconds by loading via memory card
✔ Loadable firmware for the flexible use of further conversions
✔ With diagnosis and configuration interface via USB

826.00

Available on backorder

NT 100-RE-EN Ethernet to Ethernet supports the following protocols:

  • EtherCAT Slave
  • EtherNet/IP Adapter
  • POWERLINK Controlled Node
  • PROFINET IO-Device
  • Sercos Slave
  • EtherNet/IP Scanner
  • PROFINET IO-Controller
  • Ethernet
  • Sercos Master
  • EtherCAT Master

netTAP 100 connects to communication networks and acts as a Gateway for sophisticated conversions between one Real-Time Ethernet protocol (2-port) and one fieldbus protocol or one serial automation protocol as well as between two fieldbus protocols as well as between one fieldbus protocol and one serial automation protocol. Licensed Master functionality is unrestricted.

A memory card slot allows the user to save firmware and configuration data on a removable card. In case of problems, the user can continue operation within a few seconds by removing the memory card from the netTAP 100 and connecting it to a spare unit.

Apart from s dard protocols, netTAP 100 supports the programming of special serial protocols with the Lua-based scripting language netSCRIPT. A full-featured development environment (included within the delivery) allows the comfortable and rapid programming of any proprietary serial protocol as well as the I/O data preprocessing and further processing during the conversion into the secondary I/O field protocol.

 

IEPSOLnical Data – NT 100-RE-EN Ethernet to Ethernet:

ProductProduct nameNT 100-RE-EN
Part number1712.110
Brief descriptionGateway Real-Time-Ethernet to Ethernet
Communication controllernetXnetX 100
Integrated MemoryRAM8 MB SDRAM
FLASH4 MB serial Flash
Memory cardType and sizeSD or MMC card, max. 2 GByte
Power supplySupply voltage24 V DC ± 6 V
Maximum Current at 24 V (typically)130 mA
Typical power consumption3,2 W
ConnectorMini-COMBICON, 2-pin
Reverse voltage protectionyes
Requirement to the power supplyFor UL compliant usage: Device shall be supplied by an isolated voltage source
Communication interface X2Communication s dardEthernet
Interface type100BASE-TX or 10BASE-T, isolated
Connector2 * RJ45
Communication interface X3Communication s dardEthernet
Interface type100BASE-TX or 10BASE-T, isolated
Connector1 * RJ45
Diagnostic interfaceTypeUSB
ConnectorMini-USB, 5-pin
DisplaysLED displaysSYS System status Duo LED yellow/green
APL Application status Duo LED green/red
LINK Link LED green
ACT Activity LED yellow
LINK Link LED green (right)
ACT Activity LED yellow (right)
Permitted ambient conditionsAmbient temperature (operation)0 … + 60 °C
Humidityno condensation permitted
Pollution degreeFor UL-compliant usage: Device must be used in a pollution degree 2 environment
Altitude0 … 2000 m
DeviceDimensions (L x W x H)100 x 52 x 70 mm (without connector)
Weightappr. 150 g
Degree of protectionIP 20
Mountingon DIN rail EN 60715
ConfigurationConfiguration softwareSYCON.net
ConformityRoHSYes
UL certificationULThe device is UL 508 certified
UL fileUL-File No E334100
Conformance with EMC directivesCE signYes
UKCA signYes
EmissionCISPR 11 Class A
ImmunityEN 61131-2 / BS EN 61131-2
Electrostatic discharge (ESD) according to EN 61000-4-2 / BS EN 61000-4-2 (Air discharge method)± 8 kV, Criterion A
Electrostatic discharge (ESD) according to EN 61000-4-2 / BS EN 61000-4-2 (Contact discharge method)± 4 kV, Criterion A
Fast transient interferences (Burst), according to EN 61000-4-4 / BS EN 61000-4-4±2.5 kV Criterion A
Surge voltage, according to EN 61000-4-5 / BS EN 61000-4-5 (Communication and data lines)±1.2 kV Criterion A