Make: PR Electronics | Origin: Denmark | Condition: New
✔ Excellent accuracy, surpassing 0.1% of span
✔ Superior EMC performance with effective 50/60 Hz noise suppression
✔ Selectable response time options: under 30 ms or 300 ms
✔ Pre-calibrated temperature ranges easily set via DIP switches
✔ Slim and compact 6.1 mm housing design

130.00

Available on backorder

Description

The PR 3102 Pt100 Converter by PR Electronics is engineered to convert Pt100 RTD sensor signals into standardized analog outputs for seamless integration with automation systems. Industrial engineers trust the PR 3102 Pt100 Converter for stable and precise temperature readings, protection against electrical interference, and reliable signal transmission. Installed in control cabinets or process panels, the PR 3102 Pt100 Converter delivers dependable performance, ensuring accurate temperature monitoring across industrial applications including chemical, oil & gas, and water treatment systems.

Advanced Features

• Converts Pt100 RTD input to standard 4–20 mA output
• High-precision temperature measurement
• Galvanic isolation for system protection
• Compact DIN rail mounting
• Stable performance in industrial environments
• Easy integration with PLC and DCS systems

Applications

• PLC and DCS temperature monitoring systems
• Industrial process control panels
• Chemical, petrochemical, and oil & gas plants
• Water and wastewater treatment facilities
• Any industrial automation process requiring precise Pt100 measurement

Technical Characteristics

Mounting: DIN Rail
Input Type: Pt100 RTD
Output Signal: 4–20 mA
Function: Pt100 signal conversion and isolation
Application: Industrial temperature measurement & automation

Datasheet PR 3102 Pt100 Converter

Other
Weight0.070 kg
Dimensions115 × 6.1 × 113 cm

Environmental Conditions

Operating temperature-25°C to +70°C
Storage temperature-40°C to +85°C
Calibration temperature20…28°C
Relative humidity< 95% RH (non-cond.)
Protection degreeIP20
Installation inPollution degree 2 & measurement / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD)113 x 6.1 x 115 mm
Weight approx.70 g
DIN rail typeDIN EN 60715/35 mm
Wire size0.13 x 2.5 mm2 / AWG 26…12 stranded wire
Screw terminal torque0.5 Nm
VibrationIEC 60068-2-6
2…25 Hz±1.6 mm
25…100 Hz±4 g

Common specifications

Supply

Supply voltage16.8…31.2 VDC
Max. required power0.7 W

Response time

Response time (0…90%, 100…10%)< 30 ms / 300 ms (selectable)
Signal / noise ratio> 60 dB
ProgrammingDIP-switches
Signal dynamics, input23 bit
Signal dynamics, output18 bit
AccuracyBetter than 0.1% of selected range
EMC immunity influence< ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst< ±1% of span
Incorrect DIP-switch setting identification0 V / 0 mA output; LED 0.5 s / 1 Hz

Input specifications

RTD input

Temperature range, Pt100-200…+850°C
Min. measurement range (span)10°C
Accuracy: the greater ofBetter than 0.1% of span or 0.2°C
Temperature coefficient: the greater of0.02°C/°C or ≤ ±0.01%/°C
Sensor current< 150 µA
Sensor cable resis ce< 50 Ω per wire
Effect of sensor cable resis ce (3-/4-wire)< 0.002 Ω / Ω
Sensor error detectionYes – selectable via DIP-switch
Broken sensor detection> 800 Ω
Shorted sensor detection< 18 Ω

Output specifications

Common output specifications

Updating time10 ms

Current output

Signal range0…23 mA
Programmable signal ranges0 / 4…20 mA
Sensor error indication (0…20 mA)0 mA or 23 mA / OFF
Sensor error indication (4…20 mA)3.5 mA or 23 mA / acc. to NAMUR NE43 or OFF
Load (@ current output)≤ 600 Ω
Load stability≤ 0.01% of span / 100 Ω
Current limitation @ low output load< 60 mA peak / < 4 mA average

Voltage output

Programmable signal ranges0/1…5 and 0/2…10 V
Sensor error indication0 V / 10% above the max. / none
Load (@ voltage output)≥ 10 kΩ
Open output< 18 V

Observed authority requirements

EMC2014/30/EU
LVD2014/35/EU
RoHS2011/65/EU
EACTR-CU 020/2011

Approvals

ATEX 2014/34/EUKEMA 10ATEX0147 X
IECExKEM 10.0068X
FMFM17US0004X / FM17CA0003X
DNV-GL MarineS d. f. Certific. No. 2.4 V1-7-2
ULUL 61010-1

Data sheet