Make: PR Electronics | Origin: Denmark | Condition: New
✔ Signal isolation and conversion for standard DC inputs
✔ Fast response time below 7 ms
✔ Splitter capability: one input to two outputs
✔ Easy operation with no configuration required
✔ Compact slimline housing measuring 6.1 mm

195.00

In stock (can be backordered)

Description

The PR 3108 Isolated Repeater / Splitter from PR Electronics (Denmark) is a compact industrial signal conditioning module designed to isolate, duplicate, and transmit analog current signals in automation systems. The PR 3108 Isolated Repeater / Splitter converts a single input signal into two isolated outputs, ensuring reliable signal distribution to PLC, SCADA, and control systems. The PR 3108 Isolated Repeater / Splitter provides galvanic isolation that eliminates ground loops and protects sensitive instrumentation from electrical interference. Its slim 6.1 mm DIN-rail housing allows high-density installation in industrial control panels. Industrial buyers looking to buy PR 3108 Isolated Repeater / Splitter, find a PR Electronics distributor, or source a signal isolator replacement module benefit from its robust construction, high accuracy, and simple plug-and-play operation.

Advanced Features

  • 1 input → 2 isolated analog outputs (signal splitter)
  • High galvanic isolation for signal protection
  • Slim 6.1 mm DIN rail housing for compact panel installation
  • Fast response time < 7 ms
  • High signal accuracy and stability
  • Overvoltage and polarity protection
  • Factory-calibrated ranges with no configuration required
  • Designed for harsh industrial environments

Applications

  • Signal isolation for PLC and SCADA systems
  • Analog signal duplication (4–20 mA loops)
  • Process control and monitoring systems
  • Oil & gas and chemical processing plants
  • Marine and high-vibration environments
  • Industrial automation control panels
  • Eliminating ground loop interference

Technical Characteristics

  • Input Signal: 0–23 mA current
  • Outputs: 2 × 0–23 mA current outputs
  • Supply Voltage: 16.8 – 31.2 VDC
  • Isolation Voltage: 2.5 kVAC
  • Response Time: < 7 ms
  • Operating Temperature: –25°C to +70°C
  • Mounting: DIN rail (6.1 mm width)
  • Protection: IP20 industrial housing

Datasheet PR 3108 Isolated Repeater / Splitter

Other
Weight0.5 kg
Dimensions25 × 15 × 15 cm

Environmental Conditions

Operating temperature-25°C to +70°C
Storage temperature-40°C to +85°C
Calibration temperature20…28°C
Relative humidity< 95% RH (non-cond.)
Protection degreeIP20
Installation inPollution degree 2 & measurement / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD)113 x 6.1 x 115 mm
Weight approx.70 g
DIN rail typeDIN EN 60715/35 mm
Wire size0.13 x 2.5 mm2 / AWG 26…12 stranded wire
Screw terminal torque0.5 Nm
2…25 Hz±1.6 mm
25…100 Hz±4 g

Common specifications

Supply

Supply voltage16.8…31.2 VDC
Max. required power0.8 W
Internal power dissipation0.4 W (typ.) / 0.65 W (max.)

Isolation voltage

Isolation voltage, test / working2.5 kVAC / 300 VAC (reinforced)
Zone 2 / Div. 2250 VAC

Response time

Response time (0…90%, 100…10%)< 7 ms
Signal / noise ratio> 60 dB
AccuracyBetter than 0.05%
Temperature coefficient< ±0.01% of span / °C
EMC immunity influence< ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst< ±1% of span

Input specifications

Current input

Measurement range0…23 mA
Input voltage drop< 1.5 VDC

Output specifications

Current output

Signal range0…23 mA
Load (@ current output)≤ 300 Ω
Load stability≤ 0.01% of span / 100 Ω
Current limit≤ 28 mA
*of span= 0…20 mA

Observed authority requirements

EMC2014/30/EU
LVD2014/35/EU
RoHS2011/65/EU
EACTR-CU 020/2011

Approvals

ATEX 2014/34/EUKEMA 10ATEX0147 X
IECExKEM 10.0068X
FMFM17US0004X / FM17CA0003X
DNV-GL MarineS d. f. Certific. No. 2.4 V1-7-2
ULUL 61010-1
EAC Ex TR-CU 012/2011RU C-DK.GB08.V.00410
CCOEP337347/1

Data sheet