Dark Light

PR 3112 Pt100 Converter – Isolated

Availability:

Available on backorder


Make: PR Electronics | Origin: Denmark | Condition: New
✔ Outstanding accuracy, surpassing 0.05% of span
✔ Superior EMC performance with effective 50/60 Hz noise suppression
✔ Choice of response times: less than 30 ms or 300 ms
✔ Pre-calibrated temperature ranges easily selected via DIP switches
✔ Slimline 6.1 mm compact housing

143.00

Available on backorder

Description

The PR 3112 Pt100 Converter – Isolated from PR Electronics (Denmark) is a compact industrial signal conditioning module designed to convert RTD temperature signals from Pt100 sensors into standard analog outputs used in PLC and automation systems. The PR 3112 Pt100 Converter – Isolated ensures precise temperature signal conversion while providing galvanic isolation to protect control equipment from electrical interference. The PR 3112 Pt100 Converter – Isolated converts resistance-based temperature signals into stable 4–20 mA or voltage outputs, enabling reliable monitoring and control in industrial environments. Its slim DIN-rail design allows easy installation in high-density control panels and automation cabinets. Industrial buyers searching to buy PR 3112 Pt100 Converter – Isolated, locate a PR Electronics distributor, or find a Pt100 signal converter replacement module benefit from its high accuracy, long-term stability, and robust industrial performance.

Advanced Features

  • Designed for Pt100 RTD temperature sensors
  • Converts temperature signals to standard 4–20 mA or voltage outputs
  • Galvanic isolation between input, output, and supply
  • High precision temperature measurement
  • Slim DIN rail mounting for industrial control panels
  • Excellent EMC protection and noise immunity
  • Reliable performance in harsh industrial environments
  • Compact housing for high-density installations

Applications

  • Industrial temperature monitoring systems
  • PLC and DCS temperature signal interfacing
  • HVAC and building automation systems
  • Power plant temperature monitoring
  • Chemical and petrochemical process control
  • Manufacturing and production automation
  • RTD sensor signal conversion and isolation

Technical Characteristics

  • Input: Pt100 RTD temperature sensor
  • Output Signals: 4–20 mA / voltage output
  • Isolation: Galvanic isolation
  • Mounting: DIN rail module
  • Industrial Protection: High EMC immunity
  • Country of Origin: Denmark

Datasheet PR 3112 Pt100 Converter

Other
Weight0.070 kg
Dimensions115 × 6.1 × 113 cm

Environmental Conditions

Operating temperature-25°C to +70°C
Storage temperature-40°C to +85°C
Calibration temperature20…28°C
Relative humidity< 95% RH (non-cond.)
Protection degreeIP20
Installation inPollution degree 2 & measurement / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD)113 x 6.1 x 115 mm
Weight approx.70 g
DIN rail typeDIN EN 60715/35 mm
Wire size0.13 x 2.5 mm2 / AWG 26…12 stranded wire
Screw terminal torque0.5 Nm
VibrationIEC 60068-2-6
2…25 Hz±1.6 mm
25…100 Hz±4 g

Common specifications

Supply

Supply voltage16.8…31.2 VDC
Max. required power0.7 W

Isolation voltage

Isolation voltage, test / working2.5 kVAC / 300 VAC (reinforced)
Zone 2 / Div. 2250 VAC

Response time

Response time (0…90%, 100…10%)< 30 ms / 300 ms (selectable)
AccuracyBetter than 0.05% of selected range
Signal / noise ratio> 60 dB
ProgrammingDIP-switches
Signal dynamics, input23 bit
Signal dynamics, output18 bit
EMC immunity influence< ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst< ±1% of span
Incorrect DIP-switch setting identification0 V / 0 mA output; LED 0.5 s / 1 Hz

Input specifications

RTD input

Temperature range, Pt100-200…+850°C
Min. measurement range (span)10°C
Accuracy: the greater ofBetter than 0.05% of span or 0.1°C
Temperature coefficient: the greater of0.02°C/°C or ≤ ±0.01%/°C
Sensor current< 150 µA
Sensor cable resis ce< 50 Ω per wire
Effect of sensor cable resis ce (3-/4-wire)< 0.002 Ω / Ω
Sensor error detectionYes – selectable via DIP-switch
Broken sensor detection> 800 Ω
Shorted sensor detection< 18 Ω

Output specifications

Common output specifications

Updating time10 ms

Current output

Signal range0…23 mA
Programmable signal ranges0 / 4…20 mA
Sensor error indication (0…20 mA)0 mA or 23 mA / OFF
Sensor error indication (4…20 mA)3.5 mA or 23 mA / acc. to NAMUR NE43 or OFF
Load (@ current output)≤ 600 Ω
Load stability≤ 0.01% of span / 100 Ω
Current limitation @ low output load< 60 mA peak / < 4 mA average

Voltage output

Programmable signal ranges0/1…5 and 0/2…10 V
Sensor error indication0 V / 10% above the max. / none
Open output< 18 V

Observed authority requirements

EMC2014/30/EU
LVD2014/35/EU
RoHS2011/65/EU
EACTR-CU 020/2011

Approvals

ATEX 2014/34/EUKEMA 10ATEX0147 X
IECExKEM 10.0068X
FMFM17US0004X / FM17CA0003X
DNV-GL MarineS d. f. Certific. No. 2.4 V1-7-2
ULUL 61010-1

Data sheet


Manuals


SHOPPING CART

close

Select at least 2 products
to compare