Make: PR Electronics | Origin: Denmark | Condition: New

✔ Comprehensive Multi-Sensor Input Support
✔ Integrated 2-Wire Auxiliary Power
✔ Certified for Hazardous Locations
✔ Dual Analog Output Versatility
✔ Global Power Compatibility

222.00

Available on backorder

Description

The PR 4114 Universal Transmitter by PR Electronics is designed to convert and isolate multiple sensor signals for reliable communication in industrial control systems. Automation engineers rely on the PR 4114 Universal Transmitter to ensure accurate signal conditioning between field sensors and automation equipment. The PR 4114 Universal Transmitter supports a wide range of inputs including RTD, thermocouple, resistance, voltage, and current signals. Installed in industrial control panels, the PR 4114 Universal Transmitter ensures stable signal transmission and dependable operation in demanding process environments.

Advanced Features

• Universal programmable input configuration
• Supports RTD, thermocouple, resistance, voltage, and current signals
• High precision signal conversion
• Compact DIN rail installation
• Reliable industrial-grade performance
• Easy integration with PLC and DCS systems

Applications

• Industrial temperature and signal monitoring systems
• PLC and DCS automation panels
• Process control instrumentation
• Oil & gas and chemical processing plants
• Water and wastewater treatment facilities

Technical Characteristics

Mounting: DIN Rail
Input Types: RTD, Thermocouple, Resistance, Voltage, Current
Output Signal: Analog signal output
Application: Industrial signal conversion and automation

Datasheet PR 4114 Universal Transmitter

General Details
Brand

PR Electronics

Country of Origin

Denmark

Warranty

5 Years

Technical Details
Function

Temperature Transmitter, Universal Transmitter

Input(s)

Universal

Output(s)

DC Current, DC Voltage

Power Supply

19.2…300 VDC, 21.6…253 VAC, Universal

Dimension

109×23.5×104 mm

Communications

Bluetooth, Optional, RS-485 Modbus

Advanced Features

Calibration, Detachable Display, Password Protection, Programmable, Scaling, Simulation

Certification

DNV-GL Marine, EAC, EU RO Mutual Recognition Type Approval, FM, SIL, UL

Input Range(s)

Refer to Datasheet

Number of Inputs

1

Number of Outputs

1

Environmental Conditions

Operating temperature-20°C to +60°C
Storage temperature-20°C to +85°C
Calibration temperature20…28°C
Relative humidity< 95% RH (non-cond.)
Protection degreeIP20

Mechanical specifications

Dimensions (HxWxD)109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501 / 4511109 x 23.5 x 116 / 131 mm
Weight approx.145 g
Weight incl. 4501 / 4511 (approx.)160 g / 245 g
Wire size1 x 2.5 mm2 stranded wire
Screw terminal torque0.5 Nm
VibrationIEC 60068-2-6
2…13.2 Hz±1 mm
13.2…100 Hz±0.7 g

Common specifications

Supply

Supply voltage, universal21.6…253 VAC, 50…60 Hz or 19.2…300 VDC
Max. required power≤ 2.0 W

Isolation voltage

Isolation voltage, test / working2.3 kVAC / 250 VAC

Response time

Temperature input (0…90%, 100…10%)≤ 1 s
mA / V input (0…90%, 100…10%)≤ 400 ms

Auxiliary supplies

2-w. supply (term. 44…43)25…16 VDC / 0…20 mA
Fuse400 mA SB / 250 VAC
ProgrammingCommunication enabler 4511 / Programming front 4501
Signal / noise ratioMin. 60 dB (0…100 kHz)
AccuracyBetter than 0.1% of selected range
EMC immunity influence< ±0.5% of span
Extended EMC immunity: NAMUR NE 21, A criterion, burst< ±1% of span

Input specifications

RTD input

RTD typePt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100
Cable resis ce per wire (max.)50 Ω
Sensor currentNom. 0.2 mA
Effect of sensor cable resis ce (3-/4-wire)< 0.002 Ω / Ω
Sensor error detectionYes
Short circuit detection< 15 Ω

Linear resis ce input

Linear resis ce min….max.0 Ω…10000 Ω

Potentiometer input

Potentiometer min….max.10 Ω…100 kΩ

TC input

Thermocouple typeB, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) via ext. sensor in connector 591020…28°C ≤ ±1°C, -20…20°C / 28…70°C ≤ 2°C
CJC via internally mounted sensor±(2.0°C + 0.4°C * Δt)
Δt =Internal temperature-ambient temperature
Sensor error detectionYes
Sensor error current: When detecting / elseNom. 2 μA / 0 μA

Current input

Measurement range0…20 mA
Programmable measurement ranges0…20 and 4…20 mA
Input resis ceNom. 20 Ω + PTC 50 Ω
Sensor error detection: Loop break 4…20 mAYes

Voltage input

Measurement range0…12 VDC
Programmable measurement ranges0/0.2…1, 0/1…5, 0/2…10 VDC
Input resis ceNom. 10 MΩ

Output specifications

Current output

Signal range0…20 mA
Programmable signal ranges0…20 / 4…20 / 20…0 and 20…4 mA
Load (@ current output)≤ 800 Ω
Load stability≤ 0.01% of span / 100 Ω
Sensor error indication0 / 3.5 / 23 mA / none
NAMUR NE 43 Upscale/Downscale23 mA / 3.5 mA
Output limitation, on 4…20 and 20…4 mA signals3.8…20.5 mA
Output limitation, on 0…20 and 20…0 mA signals0…20.5 mA
Current limit≤ 28 mA

Voltage output

Signal range0…10 VDC
Programmable signal ranges0/0.2…1; 0/1…5 ; 0/2…10; 1…0.2/0; 5…1/0; 10…2/0 V
Load (@ voltage output)≥ 500 kΩ
*of span= of the currently selected measurement range

Observed authority requirements

EMC2014/30/EU
LVD2014/35/EU

Approvals

FM3025177
ULUL 508
EACTR-CU 020/2011
DNV-GL MarineS d. f. Certific. No. 2.4
EU RO Mutual Recognition Type ApprovalMRA000000Z
SILHardware assessed for use in SIL applications