Make: PR Electronics | Origin: Denmark | Condition: New

✔ Supports inputs from RTD, thermocouples (TC), ohm sensors, potentiometers, mA, and voltage signals
✔ Features two configurable alarm limits
✔ FM-approved for Division 2 hazardous area installations
✔ Equipped with two relay outputs
✔ Compatible with universal AC or DC power supply

205.00

Available on backorder

Description

The PR 4131 Universal Trip Amplifier from PR Electronics (Denmark) is a high-performance industrial module designed to monitor and amplify analog signals for overcurrent, overvoltage, and process protection applications. The PR 4131 Universal Trip Amplifier ensures reliable detection and triggers alarms or protective actions in industrial automation systems. This versatile module supports a wide range of input signals, providing adjustable thresholds and hysteresis, making it ideal for integration with PLCs, DCS, and SCADA systems. Industrial engineers looking to buy PR 4131 Universal Trip Amplifier, or source a PR Electronics distributor for a replacement trip amplifier, benefit from its high accuracy, galvanic isolation, and robust industrial performance.

Advanced Features

  • Monitors analog signals for trip/alarm conditions
  • Adjustable set points and hysteresis for flexible protection
  • Galvanic isolation between input, output, and supply
  • Wide input range supporting uni- and bipolar signals
  • High-speed response for critical protection applications
  • Compact DIN-rail housing for easy control panel installation
  • LED status indicators for alarms and faults
  • Robust EMC immunity and industrial-grade construction

Applications

  • Overcurrent and overvoltage protection
  • Industrial process monitoring and control
  • PLC, DCS, and SCADA system integration
  • Alarm triggering and safety interlocks
  • Motor and generator protection systems
  • Industrial automation panels requiring analog trip detection

Technical Characteristics

  • Input: Analog uni-/bipolar signals
  • Output: Relay or analog trip signal
  • Isolation: Galvanic isolation
  • Mounting: DIN rail module
  • Operating Temperature: –20°C to +70°C
  • Industrial Protection: High EMC immunity
  • Country of Origin: Denmark

Datasheet PR 4131 Universal Trip Amplifier

Environmental Conditions

Operating temperature-20°C to +60°C
Calibration temperature20…28°C
Relative humidity< 95% RH (non-cond.)
Protection degreeIP20

Mechanical specifications

Dimensions (HxWxD)109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501 / 4511109 x 23.5 x 116 / 131 mm
Weight approx.170 g
Weight incl. 4501 / 4511 (approx.)185 g / 270 g
Wire size1 x 2.5 mm2 stranded wire
Screw terminal torque0.5 Nm
VibrationIEC 60068-2-6
2…13.2 Hz±1 mm
13.2…100 Hz±0.7 g

Common specifications

Supply

Supply voltage, universal21.6…253 VAC, 50…60 Hz or 19.2…300 VDC
Max. required power≤ 2.0 W

Isolation voltage

Isolation voltage, test / working2.3 kVAC / 250 VAC

Response time

Temperature input (0…90%, 100…10%)≤ 1 s
mA / V input (0…90%, 100…10%)≤ 400 ms

Auxiliary supplies

2-w. supply (term. 44…43)25…16 VDC / 0…20 mA
Fuse400 mA SB / 250 VAC
ProgrammingCommunication enabler 4511 / Programming front 4501
Signal / noise ratioMin. 60 dB (0…100 kHz)
AccuracyBetter than 0.1% of selected range
EMC immunity influence< ±0.5% of span
Extended EMC immunity: NAMUR NE 21, A criterion, burst< ±1% of span

Input specifications

RTD input

RTD typePt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100
Cable resis ce per wire (max.)50 Ω
Sensor currentNom. 0.2 mA
Effect of sensor cable resis ce (3-/4-wire)< 0.002 Ω / Ω
Sensor error detectionYes
Short circuit detection< 15 Ω

Linear resis ce input

Linear resis ce min….max.0 Ω…10000 Ω

Potentiometer input

Potentiometer min….max.10 Ω…100 kΩ

TC input

Thermocouple typeB, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) via ext. sensor in connector 591020…28°C ≤ ±1°C, -20…20°C / 28…70°C ≤ 2°C
CJC via internally mounted sensor±(2.0°C + 0.4°C * Δt)
Δt =Internal temperature-ambient temperature
Sensor error detectionYes
Sensor error current: When detecting / elseNom. 2 μA / 0 μA

Current input

Measurement range0…20 mA
Programmable measurement ranges0…20 and 4…20 mA
Input resis ceNom. 20 Ω + PTC 50 Ω

Voltage input

Measurement range0…12 VDC
Programmable measurement ranges0/0.2…1, 0/1…5, 0/2…10 VDC
Input resis ceNom. 10 MΩ

Output specifications

Relay output

Relay functionsSetpoint, Window, Sensor error, Latch, Power and Off
Hysteresis0…100%
ON and OFF delay0…3600 s
Max. voltage250 VRMS
Max. current2 AAC or 1 ADC
Max. AC power500 VA
Sensor error reactionBreak / Make / Hold
*of span= of the currently selected measurement range

Observed authority requirements

EMC2014/30/EU
LVD2014/35/EU

Approvals

FM3025177
ULUL 508
EACTR-CU 020/2011
DNV-GL MarineS d. f. Certific. No. 2.4
EU RO Mutual Recognition Type ApprovalMRA000000Z