Dark Light

PR 4184 Universal Uni-/Bipolar Signal Transmitter

Availability:

Available on backorder


Make: PR Electronics | Origin: Denmark | Condition: New

✔ Measures DC inputs up to ±300 V and ±100 mA with spans as low as 25 mV / 0.5 mA
✔ Provides passive/active current output and buffered voltage output
✔ Fast response time under 20 ms with outstanding 0.05% accuracy
✔ Wide universal power supply range: 21.6–253 VAC / 19.2–300 VDC

234.00

Available on backorder

Description

The PR 4184 Universal Uni-/Bipolar Signal Transmitter from PR Electronics (Denmark) is a versatile industrial module designed to convert a wide range of uni- and bipolar input signals into standard analog outputs such as 4–20 mA or 0–10 V. The transmitter provides high-accuracy signal conversion with galvanic isolation, ensuring protection of sensitive PLC, DCS, and SCADA systems. Industrial engineers and automation professionals looking to buy PR 4184 Universal Uni-/Bipolar Signal Transmitter, find a PR Electronics distributor, or source a replacement signal transmitter, benefit from its compact DIN-rail design, adjustable input ranges, and reliable industrial performance.

Advanced Features

  • Supports uni- and bipolar analog input signals
  • Converts input to 4–20 mA or 0–10 V outputs
  • Galvanic isolation between input, output, and power supply
  • Adjustable input and output ranges for flexible installation
  • Slim DIN-rail housing for easy integration
  • High precision and long-term signal stability
  • LED indicators for operational status
  • Excellent EMC immunity for industrial environments

Applications

  • PLC, DCS, and SCADA system signal integration
  • Industrial analog signal conversion and monitoring
  • Process measurement for temperature, pressure, flow, and level
  • Alarm triggering and process control
  • Factory automation panels and control systems
  • Replacement module for industrial signal transmitters

Technical Characteristics

  • Input: Uni- and bipolar analog signals
  • Output: 4–20 mA / 0–10 V
  • Isolation: Galvanic isolation
  • Mounting: DIN rail
  • Operating Temperature: –20°C to +70°C
  • Industrial Protection: High EMC immunity

Datasheet PR 4184 Universal Uni-/Bipolar Signal Transmitter

Environmental Conditions

Operating temperature-20°C to +60°C
Storage temperature-20°C to +85°C
Calibration temperature20…28°C
Relative humidity< 95% RH (non-cond.)
Protection degreeIP20
Installation inPollution degree 2 & measurement / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD)109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501 / 4511109 x 23.5 x 116 / 131 mm
Weight approx.250 g
Weight incl. 4501 / 4511 (approx.)285 g / 350 g
DIN rail typeDIN EN 60715/35 mm
Wire size0.13…2.08 mm2 AWG 26…14 stranded wire
Screw terminal torque0.5 Nm
VibrationIEC 60068-2-6
2…13.2 Hz±1 mm
13.2…100 Hz±0.7 g

Common specifications

Supply

Supply voltage, universal21.6…253 VAC, 50…60 Hz or 19.2…300 VDC
Max. required power≤ 1.8 W nom.
Internal power dissipation≤ 2.5 W

Isolation voltage

Test voltage2.3 kVAC
Working voltage250 VAC (reinforced) / 500 VAC (basic)

Response time

Response time (0…90%, 100…10%)< 0.75 s
ProgrammingCommunication enabler 4511 / Programming front 4501
Signal dynamics, input20 bit
Signal dynamics, output18 bit
Signal / noise ratio> 60 dB
Output referred common mode rejection ratio0.02 ppm / VHz
AccuracyBetter than 0.3% of selected range*
EMC immunity influence< ±0.5% of span*
Extended EMC immunity: NAMUR NE21, A criterion, burst< ±1% of span*
of span= of selected s dard range

Input specifications

Current input

Signal range0…5 AAC / 40…400 Hz
Maximum input limit6.00 AAC @ 40°C
Programmable measurement ranges0…0.5; 0…1; 0…2.5 & 0…5 AAC
Custom configurable signal range0…5 AAC /40…400 Hz
Min. measurement range (span)0.5 AAC
Input resis ceNom. < 0.07 Ω

Voltage input

Signal range0…300 VAC / 40…400 Hz
Programmable measurement ranges0…0.5, 0…1, 0…2.83, 0…5, 0…120, 0…230 & 0…300 VAC
Custom configurable signal range0…300 VAC / 40…400 Hz
Min. measurement range (span)0.5 VAC
Input resis ceNom. 3 MΩ || 100 pF

Output specifications

Active unipolar and bipolar mA output

Programmable ranges0…20, 4…20 and S4…20 mA ±10 and ±20 mA
Direct or Inverted Action
Load (@ current output)≤ 800 Ω
V-curve function, active signals, 100-0-100%20-0-20 mA

Passive 2-wire mA output

Programmable ranges0…20 and 4…20 mA Direct or Inverted action
V-curve function, 100-0-100%20-0-20 mA
External loop supply3.5…30 V

Current output

Signal range0…23 mA (unipolar) -23…+23 mA (bipolar)
Current limit≤ 28 mA (unipolar) ± 28 mA (bipolar)
Load stability≤ 0.001% of span / 100 Ω
Response time, programmable0.0…60.0 s

Voltage output

Programmable signal ranges0/0.2…1; 0/1…5 ; 0/2…10; 1…0.2/0; 5…1/0; 10…2/0 V ±1, ±5 and ±10 V
Direct or Inverted action
V-curve function, 100-0-100%1-0-1, 5-0-5 and 10-0-10 V
Load (@ voltage output)≥ 500 kΩ
Response time, programmable0.0…60.0 s

Observed authority requirements

EMC2014/30/EU
LVD2014/35/EU
RoHS2011/65/EU

Approvals

ULUL 508 / C22.2 no. 14

NB

* / **For custom configurable signal ranges, general accuracy and EMC specifications are 0.3% of full scale