Dark Light
,

PR 4511Configurator

Availability:

Available on backorder


Make: PR Electronics | Origin: Denmark | Condition: New

✔ Model 4511 programming display designed for System 4000 and 9000 series devices
✔ RS-485 communication interface supporting Modbus RTU protocol
✔ Integrated display allows monitoring of live process values
✔ Provides high galvanic isolation up to 2.5 kV from the host unit
✔ Equipped with a shielded RJ45 connector located on the top

118.00

Available on backorder

Application

  • The 4511 detachable display adds Modbus RTU RS-485 serial communications to all current and future 4000/9000 units.
  • The unit converts a wide array of sensors and analog device signals measured by the system 4000 like uni- and bipolar mA and voltage signals, potentiometer, Lin. R, RTD and TC, to a Modbus communication line signal.
  • When mounted on a system 9000 device any signal coming from or going to I.S. classified area, like AI, AO, DI and DO signals, can be converted to a Modbus network.
  • All individual unit operating parameters can easily and quickly be configured by using the Modbus communication or by using the front display menu.
  • The easily readable 4511 display can be used to read the process signal, simulate the output signal, indicate sensor errors and internal device errors.

Technical Characteristics

  • 4511 has full 4501 functionality for unit programming, process signal monitoring and diagnostics handling.
  • Modbus RTU protocol is supported using a serial RS-485 communication wiring.
  • Multidrop half-duplex connection via shielded RJ45 connector.
  • High safe galvanic isolation of 2.5 kVAC between the serial wiring and the connected system 4000/9000 units.
  • Modbus parameters such as address, baud rate, stop bit(s), and parity bit are configured from the 4511 display, which also stores parameters.

Mounting / installation / programming

  • Mounting in Zone 2 / Div 2.
  • The 4511 can be moved from one device to another. The individual system 4000/9000 unit configuration of the first device can be saved and downloaded to subsequent devices.
  • Programmed parameters can be protected by a userdefined password.
  • When mounted on devices that are installed upside down, a menu item allows the display on the 4511 to be rotated 180o and the up/down buttons to switch function.

Environmental Conditions

Operating temperature-20°C to +60°C
Storage temperature-20°C to +85°C
Relative humidity< 95% RH (non-cond.)
Protection degreeIP20
Installation inPollution degree 2 & measurement / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD)73.2 x 23.3 x 26.5 mm
Dimensions (HxWxD) w/ 4000/9000 unit109 x 23.5 x 131 mm
Weight approx.100 g
ConnectionRJ45 – shielded

Common specifications

Supply

Max. required power≤ 0.15 W

Isolation voltage

Isolation voltage, test / working2.5 kVAC / 250 VAC reinforced isolation

Response time

Response time< 20 ms
Signal / noise ratio> 60 dB
Update rate> 50 Hz
Extended EMC immunity: NAMUR NE 21, A criterion, burstNo loss of communication
Signal typeRS-485 half duplex
Serial protocolModbus RTU
Modbus modeRTU – slave
Devices on an RS485 lineUp to 32 (w/o a repeater)
Data rates, baud2400, 4800, 9600, 19200, 38400, 57600, 115200
Automatic baudrate detectionYes – can be configured ON or OFF
ParityEven, Odd, None
Stop bit(s)1 or 2
Digital addressing1…247
Response delay0…1000 ms

Observed authority requirements

EMC2014/30/EU
LVD2014/35/EU

Approvals

DNV-GL MarineS d. f. Certific. No. 2.4
ATEX 2014/34/EUDEKRA 13ATEX0098 X
IECExDEK 13.0026 X
FM0003049132-C
ULUL 61010-1
EACTR-CU 020/2011