Dark Light

PR 5331D Temperature Transmitter

Availability:

Available on backorder


2-wire programmable transmitter

Model: 5331D3B
Make: PR Electronics
Origin: Denmark

  • RTD, TC, Ohm, or mV input
  • Extremely high measurement accuracy
  • 1.5 kVAC galvanic isolation
  • Programmable sensor error value
  • For DIN form B sensor head mounting
           

 

 

 

307.00

Available on backorder

Application

  • Linearized temperature measurement with Pt100…Pt1000, Ni100…Ni1000, or TC sensor.
  • Conversion of linear resis ce variation to a s dard analog current signal, for ins ce from valves or Ohmic level sensors.
  • Amplification of a bipolar mV signal to a s dard 4…20 mA current signal.

IEPSOLnical characteristics

  • Within a few seconds the user can program PR5331D to measure temperatures within all ranges defined by the norms.
  • The RTD and resis ce inputs have cable compensation for 2-, 3- and 4-wire connection.
  • Continuous check of vital stored data for safety reasons.

Mounting / installation

  • For DIN form B sensor head mounting.

Environmental Conditions

Operating temperature-40°C to +85°C
Calibration temperature20…28°C
Relative humidity< 95% RH (non-cond.)
Protection degree (encl./terminal)IP68 / IP00

Mechanical specifications

DimensionsØ 44 x 20.2 mm
Weight approx.50 g
Wire size1 x 1.5 mm2 stranded wire
Screw terminal torque0.4 Nm
VibrationIEC 60068-2-6
2…25 Hz±1.6 mm
25…100 Hz±4 g

Common specifications

Supply

Supply voltage7.2…30 VDC
Internal power dissipation25 mW…0.7 W

Isolation voltage

Isolation voltage, test / working1.5 kVAC / 50 VAC

Response time

Response time (programmable)1…60 s
Voltage drop7.2 VDC
Warm-up time5 min.
ProgrammingLoop Link
Signal / noise ratioMin. 60 dB
EEprom error check< 3.5 s
AccuracyBetter than 0.05% of selected range
Signal dynamics, input20 bit
Signal dynamics, output16 bit
Effect of supply voltage change< 0.005% of span / VDC
EMC immunity influence< ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst< ±1% of span

Input specifications

Common input specifications

Max. offset50% of selected max. value

RTD input

RTD typePt100, Ni100, lin. R
Cable resis ce per wire (max.)5 Ω
Sensor currentNom. 0.2 mA
Effect of sensor cable resis ce (3-/4-wire)< 0.002 Ω / Ω
Sensor error detectionYes

Linear resis ce input

Linear resis ce min….max.0 Ω…5000 Ω

TC input

Thermocouple typeB, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC)< ±1.0°C
Sensor error detectionYes
Sensor error current: When detecting / elseNom. 33 μA / 0 μA

Voltage input

Measurement range-12…800 mV
Min. measurement range (span)5 mV
Input resis ce10 MΩ