Dark Light
,

PR 5335D HART Temperature Transmitter

Availability:

Available on backorder


Make: PR Electronics | Origin: Denmark | Condition: New

✔ Accepts RTD, TC, Ohm, or mV input signals
✔ Provides very high measurement accuracy
✔ Supports HART 5 communication protocol
✔ Includes galvanic isolation for safe signal separation
✔ Suitable for installation in DIN Form B sensor heads

459.00

Available on backorder

Application

  • Linearized temperature measurement with Pt100…Pt1000, Ni100…Ni1000, or TC sensor.
  • Difference or average temperature measurement of 2 resis ce or TC sensors.
  • Conversion of linear resis ce variation to a s dard analog current signal, for ins ce from valves or Ohmic level sensors.
  • Amplification of a bipolar mV signal to a s dard 4…20 mA current signal.
  • Connection of up to 15 transmitters to a digital 2-wire signal with HART communication.

Technical Characteristics

  • Within a few seconds the user can program PR5335D to measure temperatures within all ranges defined by the norms.
  • The RTD and resis ce inputs have cable compensation for 2-, 3- and 4-wire connection.
  • The 5335D has been designed according to strict safety requirements and is therefore suitable for application in SIL 2 installations.
  • Continuous check of vital stored data for safety reasons.
  • Sensor error detection according to the guidelines in NAMUR NE89.

Mounting / installation

  • For DIN form B sensor head mounting.

Environmental Conditions

Operating temperature-40°C to +85°C
Calibration temperature20…28°C
Relative humidity< 95% RH (non-cond.)
Protection degree (encl./terminal)IP68 / IP00

Mechanical specifications

DimensionsØ 44 x 20.2 mm
Weight approx.50 g
Wire size1 x 1.5 mm2 stranded wire
Screw terminal torque0.4 Nm
VibrationIEC 60068-2-6
2…25 Hz±1.6 mm
25…100 Hz±4 g

Common specifications

Supply

Supply voltage8.0…30 VDC

Isolation voltage

Isolation voltage, test / working1.5 kVAC / 50 VAC

Response time

Response time (programmable)1…60 s
Warm-up time30 s
ProgrammingLoop Link & HART
Signal / noise ratioMin. 60 dB
AccuracyBetter than 0.05% of selected range
Signal dynamics, input22 bit
Signal dynamics, output16 bit
Effect of supply voltage change< 0.005% of span / VDC
EMC immunity influence< ±0.1% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst< ±1% of span

Input specifications

Common input specifications

Max. offset50% of selected max. value

RTD input

RTD typePt100, Ni100, lin. R
Cable resis ce per wire (max.)5 Ω (up to 50 Ω per wire is possible with reduced measurement accuracy)
Sensor currentNom. 0.2 mA
Effect of sensor cable resis ce (3-/4-wire)< 0.002 Ω / Ω
Sensor error detectionYes

TC input

Thermocouple typeB, E, J, K, L, N, R, S, T, U, W3, W5
Cold junction compensation (CJC)< ±1.0°C
Sensor error detectionYes
Sensor error current: When detecting / elseNom. 33 μA / 0 μA

Voltage input

Measurement range-800…+800 mV
Min. measurement range (span)2.5 mV
Input resis ce10 MΩ

Output specifications

Current output

Signal range4…20 mA
Min. signal range16 mA
Load (@ current output)≤ (Vsupply – 8) / 0.023 [Ω]
Load stability≤ 0.01% of span / 100 Ω
Sensor error indicationProgrammable 3.5…23 mA
NAMUR NE43 Upscale/Downscale23 mA / 3.5 mA
*of span= of the presently selected range

Observed authority requirements

EMC2014/30/EU
EACTR-CU 020/2011

Approvals

ATEX 2014/34/EUKEMA 03ATEX1537
IECExKEM 10.0083X
FMFM17US0013X
CSA1125003
INMETRONCC 12.0844 X
EAC Ex TR-CU 012/2011RU C-DK.GB08.V.00410
DNV-GL MarineS d. f. Certific. No. 2.4
SILHardware assessed for use in SIL applications