Dark Light
, , , ,

PR 9106B HART Transparent Repeater

Availability:

Available on backorder


Make: PR Electronics | Origin: Denmark | Condition: New
Variants: 9106B1A | 9106B2A | 9106B1B | 9106B2B

✔ Intrinsically Safe (IS) Barrier
✔ Full HART signal transparency
✔ Reliable signal isolation
✔ Compact DIN rail installation
✔ High accuracy signal repeating
✔ Detachable display for monitoring & troubleshooting

Price range: €323.00 through €448.00

Description

The PR 9106B HART Transparent Repeater developed by PR Electronics is designed to repeat and isolate analog signals without interrupting HART communication between field devices and control systems. The PR 9106B HART Transparent Repeater allows seamless data transfer across industrial control networks while protecting sensitive equipment from electrical disturbances. By ensuring complete HART transparency, the PR 9106B HART Transparent Repeater supports remote configuration, diagnostics, and monitoring of field transmitters. Used in control cabinets and instrumentation panels, the PR 9106B HART Transparent Repeater enhances system reliability and signal integrity in demanding industrial environments.

Advanced Features

• HART transparent signal transmission
• Supports standard 4–20 mA current loops
• High galvanic isolation between circuits
• Excellent signal stability and accuracy
• Compact DIN rail mounting design
• Suitable for hazardous and demanding environments

Applications

• Process automation and instrumentation systems
• PLC and DCS signal interface panels
• Oil & gas processing facilities
• Chemical and petrochemical plants
• Water treatment and utility monitoring systems

Technical Characteristics

Mounting: DIN Rail
Signal Type: 4–20 mA with HART communication
Function: Signal repeating and galvanic isolation
Application: Industrial process automation and instrumentation

Datasheet PR 9106B HART Transparent Repeater

Other
Loop Supply

25.3V, 27.5V

Channel(s)

A: Single, B: Double

Weight1.5 kg
Dimensions25 × 15 × 17 cm

Environmental Conditions

Operating temperature-20°C to +60°C
Storage temperature-20°C to +85°C
Calibration temperature20…28°C
Relative humidity< 95% RH (non-cond.)
Protection degreeIP20
Installation inPollution degree 2 & meas. / overvoltage cat. II

Mechanical specifications

Dimensions (HxWxD)109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501/451x109 x 23.5 x 116 / 131 mm
Weight approx.250 g
Weight incl. 4501 / 451x (approx.)265 g / 280 g
DIN rail typeDIN EN 60715/35 mm
Wire size0.13…2.08 mm2 AWG 26…14 stranded wire
Screw terminal torque0.5 Nm
VibrationIEC 60068-2-6
2…13.2 Hz±1 mm
13.2…100 Hz±0.7 g

Common specifications

Supply

Supply voltage19.2…31.2 VDC
Fuse1.25 A SB / 250 VAC
Max. required power≤ 1.1 W / ≤ 1.9 W (1 ch. / 2 ch.)
Max. power dissipation, 1 / 2 ch.≤ 0.8 W / ≤ 1.2 W

Isolation voltage

Test /working: Input to any2.6 kVAC / 300 VAC reinforced isolation
Analog output to supply2.6 kVAC / 300 VAC reinforced isolation
Status relay to supply1.5 kVAC / 150 VAC reinforced isolation

Response time

Response time (0…90%, 100…10%)< 5 ms
ProgrammingPR 4500 communication interfaces
Signal dynamics, inputAnalog signal chain
Signal dynamics, outputAnalog signal chain
SMART bi-directional communication frequency range0.5…7.5 kHz
Signal / noise ratio> 60 dB
AccuracyBetter than 0.1% of sel. range
mA, absolute accuracy≤ ±16 μA
mA, temperature coefficient≤ ±1.6 μA / °C
Effect of supply voltage change on output (nom. 24 VDC)< ±10 μA
EMC immunity influence< ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst< ±1% of span

Input specifications

Current input

Measurement range3.5…23 mA
2-wire transmitter supply 9106B1x (Uo = 27.5 VDC)>16 V / 20 mA
2-wire transmitter supply 9106B2x (Uo = 25.3 VDC)>15 V / 20 mA
Sensor error detection: Loop break 4…20 mA< 1 mA
Input voltage drop, supplied unit< 4 V @ 23 mA
Input voltage drop, non-supplied unit< 6 V @ 23 mA

Output specifications

Current output

Signal range3.5…23 mA
Load (@ current output)≤ 600 Ω
Load stability≤ 0.01% of span / 100 Ω
Current limit≤ 28 mA

Passive 2-wire mA output

Effect of external 2-wire supply voltage variation< 0.005% of span / V
Max. external 2-wire supply26 VDC

Status relay

Relay functionN.C.
Programmable low setpoint0…29.9 mA
Programmable high setpoint0…29.9 mA
Hysteresis for setpoints0.1 mA
Max. voltage125 VAC / 110 VDC
Max. current0.5 AAC / 0.3 ADC
Max. voltage – hazardous installation32 VDC / 32 VAC
Max. current – hazardous installation1 ADC / 0.5 AAC
of span= normal measurement range 4…20 mA

Observed authority requirements

EMC2014/30/EU
LVD2014/35/EU
ATEX2014/34/EU
RoHS2011/65/EU
EACTR-CU 020/2011
EAC ExTR-CU 012/2011

Approvals

ATEXDEKRA 11ATEX0244 X
IECExDEK 11.0084X
c FM usFM16US0465X / FM16CA0213X
INMETRODEKRA 16.0001 X
c UL us, UL 61010-1E314307
c UL us, UL 913E233311 (only 9106xxx-U9)
CCC2020322309003231
EAC ExRU C-DK.HA65.B.00355/19
DNV MarineTAA00000JD
ClassNKTA18527M
SILSIL 2 / SIL 3 certified & fully assessed acc. to IEC 61508

You may also like…

SHOPPING CART

close

Select at least 2 products
to compare