RTD type |
Pt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100 |
Cable resistance per wire (max.) |
50 Ω |
Sensor current |
Nom. 0.2 mA |
Effect of sensor cable resistance (3-/4-wire) |
< 0.002 Ω / Ω |
Sensor error detection |
Yes |
Short circuit detection |
< 15 Ω |
Linear resistance min….max. |
0 Ω…10000 Ω |
Potentiometer min….max. |
10 Ω…100 kΩ |
Thermocouple type |
B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
Cold junction compensation (CJC) via ext. sensor in connector 5910 |
20…28°C ≤ ±1°C, -20…20°C / 28…70°C ≤ 2°C |
CJC via internally mounted sensor |
±(2.0°C + 0.4°C * Δt) |
Δt = |
Internal temperature-ambient temperature |
Sensor error detection |
Yes |
Sensor error current: When detecting / else |
Nom. 2 μA / 0 μA |
Measurement range |
0…20 mA |
Programmable measurement ranges |
0…20 and 4…20 mA |
Input resistance |
Nom. 20 Ω + PTC 50 Ω |
Measurement range |
0…12 VDC |
Programmable measurement ranges |
0/0.2…1, 0/1…5, 0/2…10 VDC |
Input resistance |
Nom. 10 MΩ |